SA403 220VAC 3 Point Floating

SA403 uses a 220V AC, four-wire connection for three-point or floating-point control. The actuator has clockwise (CW) and counter-clockwise (CCW) control inputs: one opens the valve and the other closes it. With neither input powered, the actuator stays in its last position.

Wiring Diagram

SA403 220V AC floating-point circuit: black neutral, red close input, green open input and ground wire to earth
SA403 — 220V AC, four-wire floating-point control.

Wire Connections

Disconnect power before making or changing connections.

  • Connect the black wire to 220V AC neutral.
  • Connect the red wire to 220V AC phase to close the valve.
  • Connect the green wire to 220V AC phase to open the valve.
  • Connect the ground wire to the power source's ground/earth.

Important: Do not apply phase to the red and green wires simultaneously. Doing so will damage the actuator.