SA503 220V AC Modulating with Analog 4-20mA Signal

SA503 is a 220V AC modulating connection for motorized valves, controlled by a 4–20mA analog input signal. This wiring model has no feedback function.

Wiring Diagram

SA503 220V AC modulating circuit with red phase, black neutral, green and yellow 4–20mA input, and blue earth wire
SA503 — 220V AC supply with a 4–20mA analog input.

Wire Connections

Disconnect power before making or changing connections.

  • Connect 220V AC phase to the red wire.
  • Connect 220V AC neutral to the black wire.
  • Connect the green wire to the positive (+) 4–20mA signal terminal.
  • Connect the yellow wire to the negative (−) 4–20mA signal terminal.
  • Keep the 220V AC supply connected during normal operation.
  • Connect the blue wire to ground/earth for safety.

How to Connect an Analog Input Signal

The analog input controls the valve position. A suitable 4–20mA signal may come from a pressure sensor, temperature sensor, flow sensor or level transmitter.

If the sensor output needs conversion or adjustment, use an appropriate controller. For example, an RTD temperature probe can connect to a temperature controller that converts the probe input into a 4–20mA output based on the configured low and high temperature setpoints. This output can then control the modulating valve.

Safety: Follow the relevant electrical safety guidelines. Consult a qualified electrician if you are unsure about connecting the actuator or any other electrical device.